Your new White Rodgers 5-Day/2-Day Digital Thermostat uses the technology of a solid-state microcomputer to provide precise time/temperature control. This thermostat offers you the flexibility to design heating and cooling programs that fit your needs. LCD continuously displays set point, and alternately displays time and room temperature. Temperature override until next program period. Manual program override (HOLD temperature). User may select either 12- or 24-hour clock display. °F/°C convertibility. Battery powered (3 “AA” Energizer® alkaline batteries included). Temperature range 45° to 90°F. Standard five terminals for single or two-transformer systems. Separate 5-day (weekday) and 2-day (weekend) programming. Simultaneous heat and cool program storage. Preprogrammed temperature control. B and O terminals for single stage heat pumps or damper operation. Four separate time/temperature settings per 24-hour period. Below are the key specifications, installation, operation, programming, and troubleshooting instructions.
Assemble tools: screwdriver, wire stripper. FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
This thermostat is intended for use with a low voltage system; do not use this thermostat with a line voltage system. If in doubt about whether your wiring is millivolt, line, or low voltage, have it inspected by a qualified heating and air conditioning contractor or electrician.
The thermostat consists of two parts: the thermostat cover and the base. To remove the cover, gently pull it straight out from the base. To replace the cover, line up the cover with the base and press gently until the cover snaps onto the base.
The Thermostat Buttons and Switches:
The Display:
Figure 11. Thermostat display, buttons, and switches
Diagram showing buttons labeled 1-8, including MO TU WE TH FR, AM, SA SU, HEAT, COOL, BATTERY, HOLD, VIEW PRGM, RUN PRGM, SET TIME, FAN ON AUTO, SYSTEM COOL OFF HEAT, and temperature arrows.
Shut off electricity at the main fuse box until installation is complete. Ensure that the electrical power is disconnected. Remove the front cover of the old thermostat. With wires still attached, remove wall plate from the wall. If the old thermostat has a wall mounting plate, remove the thermostat and the wall mounting plate as an assembly. Identify each wire attached to the old thermostat using the labels enclosed with the new thermostat. Disconnect the wires from the old thermostat one at a time. DO NOT LET WIRES FALL BACK INTO THE WALL.
Remove the packing material from the thermostat. Gently pull the cover straight off the base. Forcing or prying on the thermostat will cause damage to the unit.
Figure 3. Typical wiring diagram for heating only, 2-wire, single transformer systems or millivolt systems
Diagram shows THERMOSTAT connected to SYSTEM with terminals Y, B, O, G, W, RC, RH. JUMPER WIRE between RC and RH. Connected to Heating System, Fan Relay, 24 VAC Transformer, 120 VAC Hot, Neutral or Thermopile. NOTE: RED jumper wire (provided with thermostat) must be connected between thermostat's RH and RC terminals for proper thermostat operation with this system.
Figure 4. Typical wiring diagram for 3-wire SERIES 10 heating systems
Diagram shows THERMOSTAT with terminals Y, B, O, G, W, RC, RH connected to SYSTEM. 3-wire Series 10 Primary Control (located at furnace) with R, W, B. Heating System, Cooling System Relay, System Fan. 24 VAC, 120 VAC Hot, Neutral. Furnace. Add jumper wire (not provided with thermostat) between R and B terminals on the primary control. NOTE: Jumper wire must be added between R and B terminals on the primary control (jumper wire not provided with thermostat).
Figure 5. Typical wiring diagram for heat only, 3-wire, single transformer systems
Diagram shows THERMOSTAT with terminals Y, B, O, G, W, RC, RH connected to SYSTEM. JUMPER WIRE and JUMPER WIRE. Heating System, Fan Relay. Hot, 24 VAC, 120 VAC Neutral. TRANSFORMER.
Figure 6. Typical wiring diagram for cool only, 3-wire, single transformer systems
Diagram shows THERMOSTAT with terminals Y, B, O, G, W, RC, RH connected to SYSTEM. JUMPER WIRE and JUMPER WIRE. Cooling System, Fan Relay. Hot, 24 VAC, 120 VAC Neutral. TRANSFORMER.
Figure 7. Typical wiring diagram for heat/cool, 4-wire, single transformer systems
Diagram shows THERMOSTAT connected to SYSTEM with terminals Y, B, O, G, W, RC, RH. JUMPER WIRE between RC and RH. Connected to Cooling System, Fan Relay, Heating System. 24 VAC Transformer, 120 VAC Hot, Neutral. NOTE: RED jumper wire (provided with thermostat) must be connected between thermostat's RH and RC terminals for proper thermostat operation with this system.
Figure 8. Typical wiring diagram for heat/cool, 5-wire, two-transformer systems
Diagram shows THERMOSTAT with terminals Y, B, O, G, W, RC, RH connected to SYSTEM. Heating System, Fan Relay, Cooling System Relay. HEATING TRANSFORMER (Hot, 24 VAC, 120 VAC Neutral, W), COOLING TRANSFORMER (Hot, 24 VAC, 120 VAC Neutral, R). Furnace.
Figure 9. Typical wiring diagram for heat pump with cool active reversing valve
Diagram shows THERMOSTAT with terminals Y, B, O, G, W, RC, RH connected to SYSTEM. Reversing Valve*, Compressor Contactor, Fan Relay. JUMPER WIRE between RC and RH. Hot, 24 VAC, 120 VAC Neutral. TRANSFORMER. *Reversing valve is energized when the system switch is in the COOL position. NOTE: RED jumper wire (provided with thermostat) must be connected between thermostat's RH and RC terminals for proper thermostat operation with this system.
Figure 10. Typical wiring diagram for heat pump with heat active reversing valve
Diagram shows THERMOSTAT with terminals Y, B, O, G, W, RC, RH connected to SYSTEM. Reversing Valve*, Compressor Contactor, Fan Relay. JUMPER WIRE and JUMPER WIRE. Hot, 24 VAC, 120 VAC Neutral. TRANSFORMER. *Reversing valve is energized when the system switch is in the HEAT position.
NOTE: To prevent static discharge problems, touch side of thermostat to release static build-up before touching any keys. If at any time during testing your system does not operate properly, contact a qualified service person.
If your system does not have a G terminal connection, skip to Heating System.
CAUTION: To prevent compressor and/or property damage, if the outdoor temperature is below 50°F, DO NOT operate the cooling system.
This thermostat has a built-in short-term (5-minute) time delay. This feature is activated after the compressor shuts down and the setpoint is changed within the 5-minute period. During this 5-minute period, COOL will flash on the display indicating that the thermostat has locked out the compressor to allow head pressure to stabilize. This thermostat does not sense AC power loss and therefore does not activate the short term compressor protection feature when power is restored.
This section will help you plan your thermostat’s program to meet your needs. For maximum comfort and efficiency, keep the following guidelines in mind when planning your program. When heating (cooling) your building, program the temperatures to be cooler (warmer) when the building is vacant or during periods of low activity. During early morning hours, the need for cooling is usually minimal.
Look at the factory preprogrammed times and temperatures shown below. If this program will suit your needs, simply press the RUN PRGM button to begin running the factory preset program.
Set Current Time and Day
Enter Heating Program
Enter Cooling Temperatures
CAUTION: If the outside temperature is below 50°F, disconnect power to the cooling system before programming. Energizing the air conditioner compressor during cold weather may cause personal injury or property damage.
Check your programming
SAMPLE Heating/Cooling Schedule Plan (Factory Program)
| Period | WEEKDAYS (5 Day) Start Time | WEEKDAYS Temp | WEEKEND (2 Day) Start Time | WEEKEND Temp |
|---|---|---|---|---|
| 1ST | 6:00 AM | 70 F | 6:00 AM | 70 F |
| 2ND | 8:00 AM | 62 F | 8:00 AM | 70 F |
| 3RD | 5:00 PM | 70 F | 5:00 PM | 62 F |
| 4TH | 10:00 PM | 62 F | 10:00 PM | 62 F |
| Symptom | Possible Cause | Corrective Action |
|---|---|---|
| No Heat/No Cool/No Fan (common problems) | 1. Blown fuse or tripped circuit breaker. 2. Furnace power switch to OFF. 3. Furnace blower compartment door or panel loose or not properly installed. | 1. Replace fuse or reset breaker. 2. Turn switch to ON. 3. Replace door panel in proper position to engage safety interlock or door switch. |
| No Heat | 1. Pilot light not lit. 2. Loose connection to thermostat or system. 3. Thermostat or heating system requires replacement or service. 4. SYSTEM Switch not set to HEAT. | 1. Re-light pilot. 2. Verify thermostat and system wires are securely attached. 3. Your furnace manufacturer or service person can describe how to test the heating system to verify it is operating correctly. If the heating system is capable of operation and the no heat condition persists, replace the thermostat. 4. Set SYSTEM Switch to HEAT and raise temp above room temp. |
| No Cool | 1. Loose connection to thermostat or system. 2. Thermostat or cooling system requires replacement or service. 3. SYSTEM Switch not set to COOL. | 1. Verify thermostat and system wires are securely attached. 2. Your cooling system manufacturer or service person can describe how to test the cooling system to verify it is operating correctly. If the cooling system is capable of operation and the no cooling condition persists, replace the thermostat. 3. Set SYSTEM Switch to COOL and lower temp below room temp. |
| Heat, Cool or Fan Runs Constantly | 1. Possible short in wiring. 2. Possible short in thermostat. 3. Possible short in heat/cool/fan system. | Check each wire connection to the thermostat to verify it is neatly looped under the terminals. No extra wire should stick out from under the terminals. |
| Furnace Cycles Too Fast or Too Slow (narrow or wide temperature swing) | The cycle rate is fixed. The location of the thermostat, size of the Heat/Cool System and current draw can influence the cycle rate. Contact a local service person for additional suggestions. | |
| Cooling Cycles Too Fast or Too Slow (narrow or wide temperature swing) | 1. Poor thermostat location for sensing room temperature. 2. Cooling system over or undersized. 3. Excessive Current draw influencing thermostat. | The cycle rate for cooling can not be adjusted. The location of the thermostat, size of the Cool system and current draw can influence the cycle rate. Contact a local service person for suggestions. |
| Thermostat Setting and Thermostat Thermometer Disagree | 1. Thermostat thermometer setting requires adjustment. | The thermometer can be adjusted by using a standard slotted screwdriver. Turn the thermometer pointer screw located inside the front cover to change the setting. For calibrating the setting lever contact a local heating and cooling service person. |
| Blank Display and/or Keypad Not Responding | Battery or RC wire problem. | Replace batteries and check heat/cool system for proper operation. If a voltage spike occurs use the Reset Operation listed above. |