The White Rodgers 1F83-0471 is a non-programmable digital thermostat with automatic heat/cool changeover for single-stage heat/cool systems. It supports heat pumps (no auxiliary or emergency heat), heat-only, millivolt heat-only (floor or wall furnaces), cool-only, gas/oil/electric furnaces, hydronic zone heat (2/3 wires). Features large display, one-button operation, compressor protection, filter reminder, backlit display, and remote sensor support. Powered by 24 VAC (requires C common); compatible with systems up to 1A per load, 2A max total. Below are the key specifications, installation, operation, configuration, and troubleshooting instructions.
Assemble tools: hand or power drill with 3/16 inch drill bit (if needed), flat blade screwdriver, wire cutter/stripper, level, voltmeter. Shut off power to the heating and cooling system at the main fuse or circuit breaker box until installation complete. Label wires before disconnecting. This thermostat is for low voltage systems only; not for line voltage. Install away from drafts, direct sunlight, or heat sources for accurate sensing.
WARNING! Failure to read and follow all instructions carefully before installing or operating this control could cause personal injury and/or property damage. Save these instructions.
The thermostat uses solid-state technology to provide precise temperature control. Features automatic heat/cool changeover, large easy-to-read display, backlit screen, one-button operation, compressor protection (5-min), filter reminder, remote sensor support. LCD display shows room temp/setpoint/battery level, up/down arrows, SYSTEM switch (HEAT/OFF/COOL/AUTO/EMER), FAN switch (ON/AUTO). Terminals: R (hot), C (common), G (fan), Y (compressor), W (heat), O/B (changeover).
Applications:
| System Type | Supported |
|---|---|
| Heat Pump (No Aux. or Emergency Heat) | Yes |
| Systems with up to 1 Stage Heat, 1 Stage Cool | Yes |
| Heat Only Systems | Yes |
| Millivolt Heat Only Systems - Floor or Wall Furnaces | Yes |
| Cool Only Systems | Yes |
| Gas or Oil Heat | Yes |
| Electric Furnace | Yes |
| Hydronic (Hot Water) Zone Heat - 2 Wires | Yes |
| Hydronic (Hot Water) Zone Heat - 3 Wires | Yes |
| Wired Remote Temperature Sensor (Indoor or Outdoor) | Yes |
CAUTION! To prevent electrical shock/equipment damage, disconnect power at main fuse/circuit breaker until installation complete. Label wires prior to disconnection. If in doubt about wiring, consult qualified heating/air conditioning contractor.
WARNING! Do not use on circuits exceeding 24 VAC 50/60 Hz (1A per load, 2A max total); higher voltage damages control/causes shock/fire. Do not short terminals on gas valve/primary control to test; short/incorrect wiring burns out components/causes injury/property damage. Conform to NEC Class II circuits. Do not operate cooling below 50°F (compressor damage).
ATTENTION! This product does not contain mercury but may replace one that does. Do not open mercury cells; if damaged, wear non-absorbent gloves, clean up spilled mercury, place in sealed container. Refer to www.white-rodgers.com for disposal. Handle to avoid static discharge.
A standard heat/cool thermostat consists of basic parts: Cover, Base, Subbase. Label each wire with terminal designation before disconnecting. Disconnect wires one at a time; do not let fall into wall.
Remove old thermostat. Mount new base level on wall, connect wires to terminals. Push excess wire into wall, secure base, attach thermostat body. Power up and configure.
Terminal Designations: R (24V hot), C (common), Y (compressor), G (fan), W (heat), O/B (changeover), L (fault).
Single Stage Heat/Cool: R to hot, C to common, Y to compressor, G to fan, W to heat.
Heat Pump: Y compressor, O/B changeover (O cool, B heat).
Heat Only: W heat relay/valve.
Cool Only: Y compressor relay.
Millivolt: W millivolt gas valve.
Hydronic: W zone valve/circulator.
Remote Sensor: Terminals for wired sensor.
CAUTION! Refer to equipment manuals for specifics. Do not short wires.
Restore power. Set SYSTEM to HEAT/COOL, FAN to ON/AUTO, adjust setpoint to test.
CAUTION! Do not operate below 50°F.
Non-programmable thermostat. Setpoints are manually adjusted using up/down arrows. No scheduling features.
Press and hold SYSTEM button for 5 seconds to enter menu. Use up/down to adjust, SYSTEM to advance.
| Menu # | Display | Function | Options | Factory Default |
|---|---|---|---|---|
| 1 | HP SS | Heat Pump Stages | 1 | 1 |
| 2 | COOL | Cooling Stages | 1 | 1 |
| 3 | HEAT | Heating Stages | 1 | 1 |
| 4 | dS | Keypad Lockout | Off | Off |
| 5 | dF | Fahrenheit/Celsius | °F/°C | °F |
| 6 | dI | Daylight Savings | On/Off | On |
| 7 | EC | Emergency Heat Offset | 1 to 10°F | 5°F |
| 8 | AL | Alarm Temperature | 40 to 99°F | 99°F |
| Symptom | Possible Cause | Corrective Action |
|---|---|---|
| Display Blank | Power loss. | Check transformer/wiring; restore power. |
| System Not Responding | Wiring error, no power. | Verify wiring, circuit breaker; consult manual. |
| Incorrect Temperature | Calibration needed, sensor issue. | Check remote sensor; calibrate if applicable. |
| Alarm Sounds | Temperature limits exceeded. | Check settings, reset alarm. |
| Fan Not Running | AUTO no call; wiring. | Set ON; check G terminal. |
| Short Cycling | Differential settings. | Adjust in configuration menu. |
| Compressor Won't Start | Protection lockout. | Wait for delay; check flashing indicators. |
Reset Operation: Remove wires from R and C (do not short), remove batteries for 2 minutes. Resets to factory defaults.
Homeowner Help Line: 1-800-284-2925; www.white-rodgers.com