White Rodgers 1F85-0422 User Manual

The White Rodgers 1F85-0422 is a programmable electronic digital thermostat for single-stage, multi-stage, or heat pump systems with automatic heat/cool changeover option. It features 5+1+1 or 5+2 day programming, installer configuration menu, and energy-saving features like Cool Savings. Battery-powered with 2 AA batteries; compatible with 24V systems up to 1.5A per terminal. Below are the key specifications, installation, operation, programming, and troubleshooting instructions.

1. Preparations 2. Description 3. Precautions 4. Specifications 5. Installation 5.1 Wiring Diagrams 6. Check Operation 6.1 Fan Operation 6.2 Heating System 6.3 Emergency System 6.4 Cooling System 7. Operating Features 8. Programming 9. Installer Configuration 10. Troubleshooting

Preparations

Assemble tools: hand or power drill with 3/16 inch drill bit (if needed), flat blade screwdriver, wire cutter/stripper, level. Shut off electricity at main fuse box until installation complete. Label wires before disconnecting. This thermostat is for 24V systems only; not for millivolt or line voltage. Install away from drafts, direct sunlight, or heat sources for accurate sensing.

WARNING! Failure to read and follow all instructions carefully before installing or operating this control could cause personal injury and/or property damage. Save these instructions.

Description

The thermostat consists of cover and base. Features LCD display showing time/room temperature alternating with set point, up/down arrows for adjustment, SYSTEM switch (COOL/OFF/HEAT/EMER), FAN switch (ON/AUTO), O/B switch for changeover (factory "O" for COOL energized). Terminals: R, C, Y, Y2, G, W/E, W2, O/B, L. Supports heat pump with/without aux/emergency heat, up to 2-stage heat/cool, heat-only/cool-only systems.

Applications: Heat Pump (No Aux/Emergency Heat): Yes; Heat Pump (with Aux/Emergency): Yes; Standard Heat/Cool: No; Heat Only: Yes (optional fan); Millivolt Heat Only: Yes; Cool Only: Yes; Gas/Oil Heat: Yes; Electric Furnace: Yes; Hydronic 2/3 Wires: Yes.

Precautions

CAUTION! To prevent electrical shock/equipment damage, disconnect power at main fuse/circuit breaker until installation complete. Label wires prior to disconnection.

WARNING! Do not use on circuits exceeding 20-30 VAC 50/60 Hz or DC (0.05-1.5A per terminal, 2.5A max total); higher voltage damages control/causes shock/fire. Do not short terminals on gas valve/primary control to test; short/incorrect wiring burns out components/causes injury/property damage. Conform to NEC Class II circuits.

ATTENTION! This product does not contain mercury but may replace one that does. Do not open mercury cells; if damaged, wear non-absorbent gloves, clean up spilled mercury, place in sealed container. Refer to www.thermostat-recycle.org for disposal.

CAUTION! Below 50°F, do not operate cooling (compressor damage). For electric heat/single-stage heat pump, set GAS/ELEC if fan energizes on heat call. For hydronic, clip W905 for longer cycles.

Specifications

Removing Old Thermostat

A standard heat/cool thermostat consists of three basic parts: 1) Cover (snap-on/hinge type); 2) Base (loosen captive screws); 3) Switching subbase (unscrew from wall/adaptor). Label each wire with terminal designation before disconnecting. Disconnect wires one at a time; do not let fall into wall. If wall mounting plate exists, remove thermostat and plate as assembly.

Installation

Pull thermostat body off base (do not force/pry). Place base over wall hole, mark mounting holes, drill, fasten with screws (level for appearance). Connect wires to terminals. Push excess wire into wall, seal hole with fire-resistant material (e.g., fiberglass). Snap cover on.

Batteries: 2 AA alkaline (replace every 2 years; low shows battery icon/"Change Battery"). Insert positive (+) to right. For unoccupied homes >3 months, replace if icon displayed. Offset occurs when <2 months life remains (±10°F); reset manually.

Wiring Diagrams

Terminal Designations: L (malfunction indicator), O (changeover COOL), B (changeover HEAT), Y (compressor), Y2 (2nd stage compressor), W/E (heat/emergency relay stage 1), W2 (2nd stage heat/HP1), G (fan), RH (heating power), RC (cooling power), C (common), 6 (3-wire zone valve).

Single Transformer Systems: R to 24VAC hot, C to neutral, Y to compressor, G to fan, W2 to aux (stage 2), E to emergency, O/B to changeover (energized in COOL if "O"). Jumper for single aux both stages.

Two Transformer (No Safety Circuits): Separate transformers; jumper commons. Polarity observed; cut/tape unused.

Two Transformer (Safety in Both): Accessory relay N.O. for safety; jumper commons.

CAUTION! Refer to equipment manuals for specifics. Tighten securely; keep wires clear.

Check Operation

Touch side to release static before keys. Restore power. If system fails, contact serviceperson.

Fan Operation

  1. Power on.
  2. FAN ON: Blower operates.
  3. FAN AUTO: Blower stops.

Heating System

  1. SYSTEM HEAT; light pilot if standing.
  2. Adjust 1° above room: Heat pump operates ("System On", flashing if lockout).
  3. Adjust 4° above: Aux (stage 2) operates, "+2" flashing.
  4. Adjust below: Stops.

Emergency System

  1. SYSTEM EMER ("EMER" flashes).
  2. Adjust above: Aux operates, "+2" flashing.
  3. Adjust below: Stops.

Cooling System

CAUTION! Do not operate below 50°F.

  1. SYSTEM COOL.
  2. Adjust below room: Blower high, then cool ("System On").
  3. Adjust above: Stops.

Operating Features

Programming

Factory preprogrammed; RESET (back) to restore. 5+1+1 or 5+2 day; 4 periods/day.

  1. Set Time/Day: Hold SET TIME, adjust hour/min/day.
  2. Program: Hold PRGM, select day/group, adjust period time/temp (heat/cool shared times).
  3. Copy: After Mon, hold COPY to all days.
  4. Review: Hold PRGM to cycle.
  5. Run: RUN PRGM.
  6. Hold: Hold HOLD for indefinite; Temp Hold for temporary.

Factory Heat: Wake 6AM 70°F, Leave 8AM 62°F, Return 5PM 70°F, Sleep 10PM 62°F. Cool: Wake 74°F, Leave 80°F, Return 74°F, Sleep 78°F.

Installer Configuration

SYSTEM to HEAT/COOL/EMER/AUTO; hold MENU 5s. Press MENU to advance; up/down to change.

Screen #Display (Default)OptionsComments
01(OFF) Lk L-Keypad Lockout
02(000) Lk 001-999-Lockout Code
03(MS 2) HP 1, SS 1-Multi-Stage/HP/Single
04(GAS) ELE-Gas/Electric Heat
05(0) CS 1-6-Cool Savings
06(On) E OFF-EMR (1F85 only)
07(ME) CR Heat SL, FA-Heat Cycle Rate
08(ME) CR Cool SL, FA-Cool Cycle Rate
09(ME) CR HP SL, FA-HP Cycle Rate
10(FA) CR Emer SL-Emer Cycle Rate
11(OFF) CL On-Compressor Lockout
12Heat-Auto-Cool-OffVariousSystem Mode Config
13(On) dL OFF-Display Light
140 (current temp)±4Ambient Adjustment
15°F°CTemp Display
16L (90) Heat 62-89-Heat Limit
17L (45) Cool 46-82-Cool Limit
18P3 (5+1+1)P0, P2Programming Type

Troubleshooting

SymptomPossible CauseCorrective Action
Blank Display/No OperationLow batteries; power loss.Replace AA batteries; check wiring.
Heating/Cooling Not WorkingSYSTEM mode wrong; setpoint not met; wiring issue; system fault ("Call For Service").Set to HEAT/COOL, adjust setpoint; verify wires; service system.
Fan Not RunningFAN mode AUTO but no call; wiring.Set FAN ON; check G terminal.
Short CyclingCycle rate too fast; location.Adjust in config menu (slow); relocate thermostat.
Change Filter ReminderFilter time reached.Change/clean filter; reset in menu.
Compressor LockoutCycling too quick.Wait for auto-reset (5 min).