The White Rodgers 1F86-344 is a non-programmable electronic digital thermostat for 24V HVAC systems. It features simultaneous heat and cool setpoint storage, pre-set temperature control, backlit display, and LCD continuously displaying setpoint and room temperature. Compatible with standard heat/cool or heat only systems, electric heat, gas/oil fired, hydronic, single-stage heat pumps (no auxiliary heat), and millivolt systems. Requires 2 AA alkaline batteries. Below are the key specifications, installation, operation, and troubleshooting instructions.
Assemble tools required: screwdriver, wire cutter/stripper.
WARNING: Failure to read and follow all instructions carefully before installing or operating this control could cause personal injury and/or property damage.
This thermostat is intended for use with a low voltage system; do not use this thermostat with a line voltage system. If in doubt about whether your wiring is millivolt, line, or low voltage, have it inspected by a qualified heating and air conditioning contractor or electrician.
Features:
The thermostat consists of two parts: the thermostat cover and the base. To remove the cover, gently pull it straight out from the base. To replace the cover, line up the cover with the base and press gently until the cover snaps onto the base.
The Thermostat Buttons and Switches:
The Display:
Remove the packing material from the thermostat. Gently pull the cover straight off the base. Forcing or prying on the thermostat will cause damage to the unit.
NOTE: The following wiring diagrams show typical terminal identification and wiring. For proper installation, refer to the original manufacturer's instructions. * The 24 Volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” Energizer® alkaline batteries. Relay contacts shown are thermostatically operated.
Figure 3. Typical wiring diagram for single transformer systems
Thermostat terminals: C*, R, B, O, Y, G, W. System: Energized in HEAT (Heating System), Energized in COOL (Cooling System), Fan Relay. Transformer: 24 VAC (Hot, Neutral), 120 VAC. Single transformer setup with connections to heating, cooling, and fan systems.
Figure 4. Typical wiring diagram for two-transformer systems with NO safety circuits
Thermostat terminals: B, C*, R, Y, G, O, W. System: Energized in COOL (Cooling System), Energized in HEAT (Heating System), Fan Relay. Transformers: 24 VAC (Hot, Neutral) for heating, 120 VAC (Hot, Neutral) for cooling. Note: CUT AND TAPE OFF! TWO COMMONS MUST BE JUMPERED TOGETHER! Dual transformer setup without safety circuits, with jumpered commons.
Figure 5. Typical wiring diagram for two-transformer systems with safety circuits in BOTH systems
Thermostat terminals: B, C*, R, Y, G, O, W. System: Energized in COOL (Cooling System), Energized in HEAT (Heating System), Fan Relay, Accessory Relay N.O. Contact. Transformers: HEATING TRANSFORMER (24 VAC Hot, Common, Neutral), COOLING TRANSFORMER (24 VAC, 120 VAC Hot, Neutral). Safety: Limit or Safety Switches in both systems. Note: * The 24 Volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” Energizer® alkaline batteries. TWO COMMONS MUST BE JUMPERED TOGETHER! Dual transformer setup with safety circuits, including limit switches and accessory relay.
NOTE: To prevent static discharge problems, touch side of thermostat to release static build-up before touching any keys. If at any time during testing your system does not operate properly, contact a qualified service person.
If your system does not have a G terminal connection, skip to Heating System.
CAUTION: To prevent compressor and/or property damage, if the outdoor temperature is below 50°F, DO NOT operate the cooling system.
This thermostat has a built-in short-term (5-minute) time delay. This feature is activated after the compressor shuts down and the setpoint is changed within the 5-minute period. During this 5-minute period, COOL will flash on the display indicating that the thermostat has locked out the compressor to allow head pressure to stabilize. This thermostat does not sense AC power loss and therefore does not activate the short term compressor protection feature when power is restored.
| Symptom | Possible Cause | Corrective Action |
|---|---|---|
| No Heat/No Cool/No Fan (common problems) | 1. Blown fuse or tripped circuit breaker. 2. Furnace power switch to OFF. 3. Furnace blower compartment door or panel loose or not properly installed. | 1. Replace fuse or reset breaker. 2. Turn switch to ON. 3. Replace door panel in proper position to engage safety interlock or door switch. |
| No Heat | 1. Pilot light not lit. 2. Loose connection to thermostat or system. 3. Thermostat or heating system requires replacement or service. 4. SYSTEM Switch not set to HEAT. | 1. Re-light pilot. 2. Verify thermostat and system wires are securely attached. 3. Your furnace manufacturer or service person can describe how to test the heating system to verify it is operating correctly. If the heating system is capable of operation and the no heat condition persists, replace the thermostat. 4. Set SYSTEM Switch to HEAT and raise temp above room temp. |
| No Cool | 1. Loose connection to thermostat or system. 2. Thermostat or cooling system requires replacement or service. 3. SYSTEM Switch not set to COOL. | 1. Verify thermostat and system wires are securely attached. 2. Your cooling system manufacturer or service person can describe how to test the cooling system to verify it is operating correctly. If the cooling system is capable of operation and the no cooling condition persists, replace the thermostat. 3. Set SYSTEM Switch to COOL and lower temp below room temp. |
| Heat, Cool or Fan Runs Constantly | 1. Possible short in wiring. 2. Possible short in thermostat. 3. Possible short in heat/cool/fan system. | Check each wire connection to the thermostat to verify it is neatly looped under the terminals. No extra wire should stick out from under the terminals. |
| Furnace Cycles Too Fast or Too Slow (narrow or wide temperature swing) | The cycle rate is fixed. The location of the thermostat, size of the Heat/Cool System and current draw can influence the cycle rate. Contact a local service person for additional suggestions. | |
| Cooling Cycles Too Fast or Too Slow (narrow or wide temperature swing) | 1. Poor thermostat location for sensing room temperature. 2. Cooling system over or undersized. 3. Excessive Current draw influencing thermostat. | The cycle rate for cooling can not be adjusted. The location of the thermostat, size of the Cool system and current draw can influence the cycle rate. Contact a local service person for suggestions. |
| Thermostat Setting and Thermostat Thermometer Disagree | 1. Thermostat thermometer setting requires adjustment. | The thermometer can be adjusted by using a standard slotted screwdriver. Turn the thermometer pointer screw located inside the front cover to change the setting. For calibrating the setting lever contact a local heating and cooling service person. |
| Blank Display and/or Keypad Not Responding | Battery or RC wire problem. | Replace batteries and check heat/cool system for proper operation. If a voltage spike occurs use the Reset Operation listed above. |