The White Rodgers 1F90-371 is a programmable electronic digital thermostat from the Comfort-Set III series for single-stage heating/cooling systems, including gas, oil, electric, hot water/steam, millivolt, and single-stage heat pump. It features 5+2 or 5+1+1 day programming, microcomputer technology for precise control, automatic changeover, and energy-saving features like Energy Management Recovery (EMR). Powered by 24 VAC system; compatible with systems up to 1.5A total load. Below are the key specifications, installation, operation, programming, and troubleshooting instructions.
Assemble tools: hand or power drill with 3/16 inch drill bit (if needed), flat blade screwdriver, wire cutter/stripper, level. Shut off electricity at main fuse box until installation complete. Label wires before disconnecting. This thermostat is for 24V systems only; not for line voltage. Install away from drafts, direct sunlight, or heat sources for accurate sensing.
WARNING! Failure to read and follow all instructions carefully before installing or operating this control could cause personal injury and/or property damage. Save these instructions.
The thermostat uses solid-state microcomputer technology to provide precise time/temperature control. It offers flexibility to design heating and cooling programs that fit personal needs. Adaptable to most 24 Volt residential forced air, hydronic (hot water or steam), millivolt, electric heat, zone and single-stage heat pump systems. Features large lighted LCD display alternating between room temperature and time, up/down arrows for adjustment, SYSTEM switch (HEAT/OFF/COOL/AUTO), FAN switch (ON/AUTO), O/B for heat pumps.
Applications: Gas/Oil/Electric Heat: Yes; Heat Pump Single Stage: Yes; Heat Only: Yes; Cool Only: Yes; Millivolt: Yes; Hydronic: Yes.
CAUTION! To prevent electrical shock/equipment damage, disconnect power at main fuse/circuit breaker until installation complete. Label wires prior to disconnection.
WARNING! Do not use on circuits exceeding 30 VAC 50/60 Hz (1.5A max total); higher voltage damages control/causes shock/fire. Do not short terminals to test; incorrect wiring causes injury/property damage. Conform to NEC Class II circuits. Do not operate cooling below 50°F (compressor damage).
ATTENTION! This product does not contain mercury but may replace one that does. Dispose properly; refer to recycling resources.
A standard heat/cool thermostat consists of three basic parts: 1) Cover; 2) Base; 3) Subbase. Label each wire with terminal designation before disconnecting. Disconnect wires one at a time; do not let fall into wall.
Remove old thermostat. Mount new base level on wall, connect wires to terminals. For single transformer systems, install red jumper between RH and RC. Push excess wire into wall, secure base, attach thermostat body. Power up and configure.
Terminal Designations: RH/RC (power), W (heat), Y (cool/compressor), G (fan), O/B (changeover for heat pump).
Single Stage Heat/Cool: RH to hot, RC to hot (jumper RH-RC), W to heat relay, Y to compressor, G to fan.
Heat Only: Omit Y.
Cool Only: Omit W.
Heat Pump Single Stage: Y to compressor, O/B to changeover, W to aux heat if needed.
CAUTION! RED jumper wire must be connected between RH and RC for single transformer systems.
Restore power. Set SYSTEM to HEAT/COOL, FAN to ON/AUTO, adjust setpoint to test.
Not applicable for single-stage non-heat pump; for heat pump, use aux heat.
CAUTION! Do not operate below 50°F.
5+2 or 5+1+1 day; 4 periods (MOR/DAY/EVE/NHT). Factory preprogrammed; press PROGRAM + RUN to start.
Factory Heat: 6AM 70°F, 8AM 62°F, 5PM 70°F, 10PM 62°F. Cool: 6AM 78°F, 8AM 85°F, 5PM 78°F, 10PM 82°F.
Press PROGRAM + DOWN arrow for 5 seconds to enter menu. Use UP/DOWN to adjust, PROGRAM to advance.
| Menu Item | Default | Options | Comments |
|---|---|---|---|
| Ref | 0°F | ±5°F | Display temp adjustment |
| EMR | ON | OFF/L | Energy Management Recovery |
| °F/°C | °F | °C | Temperature scale |
| Fan One-Shot | 0 | 0-6 hrs | Auto fan runtime |
| Beeper | ON | OFF | Keypad sound |
| Heat Fast | OFF | ON | Fast heat cycle |
| Cool Fast | OFF | ON | Fast cool cycle |
| Outdoor Sensor | OFF | ON | Enable outdoor sensor |
| Telephone RUN | OFF | ON | X-10 phone control |
| Compressor Run Time | 00 | View/Reset | Total runtime |
| AUX Run Time | 00 | View/Reset | Aux heat runtime |
| Partial Lock | OFF | ON | Keypad partial lock |
| Total Lock | OFF | ON | Full keypad lock |
| Symptom | Possible Cause | Corrective Action |
|---|---|---|
| Display Blank | Power loss. | Check transformer/wiring; restore power. |
| CHECK SYS | System not responding (no heat rise in 2 hrs). | Retries 3 times; check system, wiring. |
| CHECK STAT | Stuck key, sensor failure. | Press PROGRAM; power cycle 5 min. |
| Heating/Cooling Not Working | Wrong mode, setpoint, wiring. | Set correct mode/setpoint; verify wires. |
| Fan Not Running | AUTO no call; wiring. | Set ON; check G terminal. |
| Short Cycling | Fast cycle setting. | Adjust in menu to OFF. |
| Compressor Won't Start | 5-min lockout. | Wait; flashing COOL indicates lockout. |