White Rodgers 1F92-71 User Manual

The White Rodgers 1F92-71 is a premium universal multi-stage heat pump digital 5/2 day programmable thermostat for multi-stage heat pump systems, including up to 3-stage heat/2-stage cool with aux/emergency heat, automatic/manual changeover. It features independent heating/cooling programs with 4 time/temperature settings per day, Computed Energy Management Recovery (EMR), and battery backup with 3 AA batteries. Powered by 24 VAC (requires hot and common); compatible with systems up to 1.5A total load. Below are the key specifications, installation, operation, programming, and troubleshooting instructions.

1. Preparations 2. Description 3. Precautions 4. Specifications 5. Installation 5.1 Wiring Diagrams 6. Check Operation 6.1 Fan Operation 6.2 Heating System 6.3 Emergency System 6.4 Cooling System 7. Operating Features 8. Programming 9. Installer Configuration 10. Troubleshooting

Preparations

Assemble tools: hand or power drill with 3/16 inch drill bit (if needed), flat blade screwdriver, wire cutter/stripper, level, voltmeter. Shut off electricity at main fuse box until installation complete. Label wires before disconnecting. This thermostat is for 24V systems only; requires both hot and common. Install about 5 ft. above floor on inside wall, away from drafts, direct sunlight, heat sources, windows, doors, registers, poor circulation areas.

WARNING! Failure to read and follow all instructions carefully before installing or operating this control could cause personal injury and/or property damage. Save these instructions.

Description

Wall-mounted, low voltage thermostat for precise multi-stage heat pump control. Microcomputer-based with 5+2 day programming, 4 periods/day, independent heat/cool programs. Features LCD display alternating time/room temp, up/down arrows, SYSTEM switch (HEAT/OFF/COOL/AUTO/EMER), FAN switch (ON/AUTO), PRGM switch, option switches for changeover/EMR/lockout. Terminals: G (fan), C (common), R (hot), O (cool changeover), B (heat changeover), Y1/Y2 (compressor stages), W1/W2/W3 (aux heat stages). Supports multi-stage heat pumps with/without aux/emergency heat.

Applications: Multi-Stage Heat Pump: Yes (up to 3H/2C); Conventional Multi-Stage: Yes; Heat Only: Yes; Cool Only: Yes; Gas/Oil/Electric/Hydronic: Yes; Millivolt: No.

Precautions

CAUTION! To prevent electrical shock/equipment damage, disconnect power at main fuse/circuit breaker until installation complete. Label wires prior to disconnection.

WARNING! Do not use on circuits exceeding 30 VAC 50/60 Hz (1.5A max total); higher voltage damages control/causes shock/fire. Do not short terminals on gas valve/primary control to test; short/incorrect wiring burns out components/causes injury/property damage. Conform to NEC Class II circuits. Do not operate cooling below 50°F (compressor damage).

ATTENTION! This product does not contain mercury but may replace one that does. Do not open mercury cells; if damaged, wear non-absorbent gloves, clean up spilled mercury, place in sealed container. Refer to www.thermostat-recycle.org for disposal.

Specifications

Removing Old Thermostat

Shut off electricity, verify with voltmeter. Remove cover, wall plate. Label wires with terminal designations (use provided labels for G,C,R,O,B,Y1,Y2,W1,W2,W3). Disconnect one at a time; pull 6 inches out; do not let fall into wall.

Installation

Program with batteries before mounting. Pull wires through subbase, connect to terminals. Place subbase over hole, mark/drill/fasten with screws (level). Push excess wire in, seal with fire-resistant material. Attach thermostat by aligning and snapping.

Batteries: Install 3 AA alkaline; low battery indicator flashes.

Wiring Diagrams

Terminal Designations: G (fan), C (common), R (24V hot), O (cool changeover), B (heat changeover), Y1 (stage 1 compressor), Y2 (stage 2 compressor), W1 (stage 1 aux heat), W2 (stage 2 aux heat), W3 (stage 3 aux heat).

Multi-Stage Heat Pump: R to hot, C to common, G to fan, Y1/Y2 to compressor stages, O/B to changeover (O for cool, B for heat), W1/W2/W3 to aux/emergency heat stages.

CAUTION! Requires R and C connected. Refer to equipment manuals for specifics. Tighten terminals securely.

Check Operation

Restore power. Set to manual changeover for testing. Override 5-min compressor lockout by holding PRGM + TEMP at startup if needed.

Fan Operation

  1. FAN ON: Blower operates.
  2. FAN AUTO: Blower stops within 1 min.

Heating System

  1. SYSTEM HEAT.
  2. Setpoint 1° above room: Compressor stage 1 operates.
  3. 3° above: Stage 2 compressor or aux stage 1.
  4. 5° above: Aux stage 2/3.
  5. Below: Stops.

Emergency System

  1. SYSTEM EMER.
  2. Setpoint above room: Aux heat stage 1 operates (EMER flashes).
  3. 5° above: Stage 2/3.
  4. Below: Stops.

Cooling System

CAUTION! Do not operate below 50°F.

  1. SYSTEM COOL.
  2. Setpoint 1° below room: Compressor stage 1 after 5-min delay.
  3. 3° below: Stage 2.
  4. Above: Stops.

Operating Features

Programming

5+2 day; 4 periods (MOR/DAY/EVE/NHT). Independent heat/cool programs. Factory preprogrammed; program with batteries installed.

  1. Set Time/Day: Press PRGM, adjust TIME arrows for hour/min, DAY for day.
  2. Program: Select HEAT/COOL, PRGM for period/group, adjust TIME/TEMP, advance PRGM.
  3. Copy: Hold COPY to duplicate.
  4. Review: PRGM + VIEW to cycle.
  5. Run: Press RUN.
  6. Hold: HOLD for permanent override; temporary 2-hour.

Factory Heat: MOR 6AM 70°F, DAY 8AM 62°F, EVE 6PM 70°F, NHT 10PM 62°F. Cool: MOR 6AM 78°F, DAY 8AM 85°F, EVE 6PM 78°F, NHT 10PM 82°F.

Installer Configuration

Set option switches on back before installing. Remove batteries when changing Group B.

GroupOptionDefaultOptionsComments
AKeypad LockoutOffOff/Limited/TotalLimited allows temp adjust only
BChangeoverAutoAuto/Manual/Heat Only/Cool OnlyAuto: 3°F deadband
BEMROnOn/OffComputed early recovery

For power failures, defaults to 64°F heat/82°F cool if program lost.

Troubleshooting

SymptomPossible CauseCorrective Action
Display BlankPower loss; dead batteries.Check R/C wiring; replace 3 AA batteries.
Battery Indicator FlashingLow batteries.Replace 3 AA; program retained.
No Heat/No CoolWrong mode; setpoint; wiring; no R/C.Set mode; adjust setpoint; verify wires/R C connected.
Fan Not RunningNo G wire; AUTO no call.Check G; set ON.
Short Cycling5-min lockout.Wait; override for testing: hold PRGM + TEMP at startup.
Program LostExtended power failure without batteries.Reprogram; defaults to 64/82°F.
Stages Not ActivatingSetpoint differential not met; config.Adjust setpoint 1°/3°/5°; check option switches.
Emergency Heat Not WorkingNot in EMER mode; wiring.Set SYSTEM EMER; check W1/W2/W3 wires.