White Rodgers 1F94-71 User Manual

The White Rodgers 1F94-71 is a 7-day programmable electronic digital thermostat for multi-stage heat/cool or heat pump systems, including up to 3-stage heat/2-stage cool, with automatic heat/cool changeover option. It features 7-day programming with 2 periods per day (occupied/unoccupied), installer configuration menu, and energy-saving features like Energy Management Recovery. Battery-powered with 3 AA batteries; compatible with 24V systems up to 1.5A per terminal. Below are the key specifications, installation, operation, programming, and troubleshooting instructions.

1. Preparations 2. Description 3. Precautions 4. Specifications 5. Installation 5.1 Wiring Diagrams 6. Check Operation 6.1 Fan Operation 6.2 Heating System 6.3 Emergency System 6.4 Cooling System 7. Operating Features 8. Programming 9. Installer Configuration 10. Troubleshooting

Preparations

Assemble tools: hand or power drill with 3/16 inch drill bit (if needed), flat blade screwdriver, wire cutter/stripper, level, voltmeter. Shut off electricity at main fuse box until installation complete. Label wires before disconnecting. This thermostat is for 24V systems only; not for millivolt or line voltage. Install away from drafts, direct sunlight, or heat sources for accurate sensing.

WARNING! Failure to read and follow all instructions carefully before installing or operating this control could cause personal injury and/or property damage. Save these instructions.

Description

The thermostat consists of cover and base. Features LCD display showing time/room temperature alternating with set point, up/down arrows for adjustment, SYSTEM switch (COOL/OFF/HEAT/EMER/AUTO), FAN switch (ON/AUTO), O/B switch for changeover (factory "O" for COOL energized). Terminals: R, C, Y, Y2, G, W/E, W2, O/B, L. Supports heat pump with/without aux/emergency heat, up to 3-stage heat/2-stage cool, heat-only/cool-only systems.

Applications: Heat Pump (No Aux/Emergency Heat): Yes; Heat Pump (with Aux/Emergency): Yes; Standard Heat/Cool: Yes; Multi-Stage: Yes; Heat Only: Yes; Millivolt Heat Only: No; Cool Only: Yes; Gas/Oil Heat: Yes; Electric Furnace: Yes; Hydronic 2/3 Wires: Yes.

Precautions

CAUTION! To prevent electrical shock/equipment damage, disconnect power at main fuse/circuit breaker until installation complete. Label wires prior to disconnection.

WARNING! Do not use on circuits exceeding 20-30 VAC 50/60 Hz or DC (0.05-1.5A per terminal, 2.5A max total); higher voltage damages control/causes shock/fire. Do not short terminals on gas valve/primary control to test; short/incorrect wiring burns out components/causes injury/property damage. Conform to NEC Class II circuits. Do not operate cooling below 50°F (compressor damage).

ATTENTION! This product does not contain mercury but may replace one that does. Do not open mercury cells; if damaged, wear non-absorbent gloves, clean up spilled mercury, place in sealed container. Refer to www.thermostat-recycle.org for disposal.

Specifications

Removing Old Thermostat

A standard heat/cool thermostat consists of three basic parts: 1) Cover (snap-on/hinge type); 2) Base (loosen captive screws); 3) Switching subbase (unscrew from wall/adaptor). Label each wire with terminal designation before disconnecting. Disconnect wires one at a time; do not let fall into wall. If wall mounting plate exists, remove thermostat and plate as assembly.

Installation

Pull thermostat body off base (do not force/pry). Place base over wall hole, mark mounting holes, drill, fasten with screws (level for appearance). Connect wires to terminals. Push excess wire into wall, seal hole with fire-resistant material (e.g., fiberglass). Snap cover on.

Batteries: 3 AA alkaline (replace every year; low shows "LOW BATT"). Insert positive (+) to right. Remove battery tags to activate.

Wiring Diagrams

Terminal Designations: L (malfunction indicator), O (changeover COOL), B (changeover HEAT), Y (compressor), Y2 (2nd stage compressor), W/E (heat/emergency relay stage 1), W2 (2nd stage heat/HP1), G (fan), RH (heating power), RC (cooling power), C (common).

Single Transformer Systems: R to 24VAC hot, C to neutral, Y to compressor, G to fan, W2 to aux (stage 2), E to emergency, O/B to changeover (energized in COOL if "O"). Jumper for single aux both stages.

Two Transformer (No Safety Circuits): Separate transformers; jumper commons. Polarity observed; cut/tape unused.

Two Transformer (Safety in Both): Accessory relay N.O. for safety; jumper commons.

CAUTION! Refer to equipment manuals for specifics. Tighten securely; keep wires clear.

Check Operation

Touch side to release static before keys. Restore power. If system fails, contact serviceperson.

Fan Operation

  1. Power on.
  2. FAN ON: Blower operates.
  3. FAN AUTO: Blower stops.

Heating System

  1. SYSTEM HEAT; light pilot if standing.
  2. Adjust 1° above room: Heat pump operates ("STG1").
  3. Adjust 3° above: Aux (stage 2) operates ("STG 1+2").
  4. Adjust below: Stops.

Emergency System

  1. SYSTEM EMER ("EMER" flashes).
  2. Adjust above: Aux operates ("STG1" "EMER").
  3. Adjust below: Stops.

Cooling System

CAUTION! Do not operate below 50°F.

  1. SYSTEM COOL.
  2. Adjust below room: Blower high, then cool ("STG1").
  3. Adjust 3° below: Stage 2 ("STG 1+2").
  4. Adjust above: Stops.

Operating Features

Programming

Factory preprogrammed 7-day; RESET to restore. 2 periods/day (OCCU/UNOC).

  1. Set Time/Day: Hold TIME, adjust hour/min/day.
  2. Program: SYSTEM HEAT/COOL, hold PRGM, select day, adjust period time/temp/weight (heat/cool shared times).
  3. Copy: Hold COPY to next day.
  4. Review: Hold PRGM to cycle.
  5. Run: RUN.
  6. Hold: Hold HOLD indefinite; Temp Hold temporary (default 4hr).

Factory Heat: OCCU 70°F, UNOC 62°F. Cool: OCCU 78°F, UNOC 85°F.

Installer Configuration

SYSTEM to OFF; hold MENU 5s. Press SYSTEM to advance; up/down to change.

StepDisplay (Default)OptionsComments
1MS2SS1, HP1, HP2System Type
2LER (OFF)ONLearn Mode
3OUTSIDE (OFF)ONOutdoor Sensor
4REMOTE (OFF)ONIndoor Remote
5LOCAL (ON)OFFLocal Sensor
6CH (0)1-9Frequency Offset
7PRG 20,2Periods
8EMR (ON)OFFRecovery
9CR (FA)SLCycle Rate
10CL (OFF)ONCompressor Lockout
11CdL (ON)OFFBacklight
12FA (ON)OFFFast Stage 2
130 FLTR50-1950Filter Timer
140 F±4Temp Adjust
154:00 HOLD0:00-8:00Temp Override
16°F°CTemp Display
17LR HEAT (90)62-89Heat Limit
18LR COOL (45)46-82Cool Limit
19CA (OFF)ONComfort Alert
20-21OFF LOCK (000)001-999Keypad Lock

Troubleshooting

SymptomPossible CauseCorrective Action
Blank Display/No OperationVoltage spike; low batteries; power loss.Reset: Remove R/C wires & batteries 2 min; replace. Press RUN+SYSTEM to factory reset.
No Heat/No Cool/No FanBlown fuse; switch OFF; door loose.Replace fuse; turn ON; secure door.
No HeatPilot out; SYSTEM not HEAT; loose wire; lock-out.Re-light; set HEAT; check wires; service furnace.
No CoolSYSTEM not COOL; loose wire.Set COOL; check wires; service.
Does Not Follow ProgramTime/day wrong; EMR early.Check AM/PM/day; disable EMR.
Fan/Heat On No CallPower stealing in PS mode.Add C wire, set RC; clip W25 if needed.
Antenna + FaultLoss of signal; wrong channel/freq; wrong ID.Check distance/channel/freq/ID; Learn Mode; replace sensor.
Temp Diff Thermostat/RemoteSystem sizing; occupancy/sun load.Adjust weight HI/LO; zone if needed.
Heat/Cool/Fan ConstantShort in wiring/thermostat/system; FAN ON.Check wires; reset; service system.
Cycles Too Fast/SlowLocation/system size.Set SL cycle; service.
Setting & Thermometer DisagreeCalibration needed.Adjust ±3°F in menu.
Heat Setpoint No UpConflicts with COOL.Set COOL higher, return HEAT.
Cool Setpoint No DownConflicts with HEAT.Set HEAT lower, return COOL.
Forgot Lockout Code-Press RUN+SYSTEM to reset/unlock.
2nd/3rd Stage No OnTime delay optimizing.Normal; 0-30 min based on stage 1.
White Rodgers 1F94-71 Thermostat Manual© - All Rights Reserved 2025