White Rodgers 1F97-0671 User Manual

The White Rodgers 1F97-0671 is a blue residential non-programmable thermostat with automatic heat/cool changeover for single-stage applications. It supports heat pumps (no auxiliary or emergency heat), heat-only, millivolt heat-only (floor or wall furnaces), cool-only, gas/oil/electric furnaces, hydronic zone heat (2/3 wires), and wired remote sensors. Features large display, one-button operation, factory pre-program option, compressor protection, filter/UV reminders. Powered by 2 AA batteries or 24 VAC; compatible with systems up to 1.5A per terminal, 2.5A max total. Below are the key specifications, installation, operation, configuration, and troubleshooting instructions.

1. Preparations 2. Description 3. Precautions 4. Specifications 5. Installation 5.1 Wiring Diagrams 6. Check Operation 6.1 Fan Operation 6.2 Heating System 6.3 Emergency System 6.4 Cooling System 7. Operating Features 8. Programming 9. Installer Configuration 10. Troubleshooting

Preparations

Assemble tools: hand or power drill with 3/16 inch drill bit (if needed), flat blade screwdriver, wire cutter/stripper, level, voltmeter. Shut off electricity at main fuse box until installation complete. Label wires before disconnecting. This thermostat is for low voltage systems only; not for line voltage. Install away from drafts, direct sunlight, or heat sources for accurate sensing. Install 2 AA alkaline batteries before use.

WARNING! Failure to read and follow all instructions carefully before installing or operating this control could cause personal injury and/or property damage. Save these instructions.

Description

The thermostat uses solid-state technology to provide precise temperature control. Features automatic heat/cool changeover, large easy-to-read display, one-button operation, wired remote indoor/outdoor sensor support, compressor protection (5-min), filter/UV lamp reminders, factory pre-program for energy savings. LCD display shows time/temp/setpoint/battery level, SYSTEM button (HEAT/OFF/COOL/EM HEAT), FAN button (ON/AUTO), up/down arrows. Terminals: R (hot), C (common), G (fan), Y (compressor), W (heat), O/B (changeover), E (emergency), L (alert).

Applications:

System TypeSupported
Heat Pump (No Aux. or Emergency Heat)Yes
Systems with up to 1 Stage Heat, 1 Stage CoolYes
Heat Only SystemsYes
Millivolt Heat Only Systems - Floor or Wall FurnacesYes
Cool Only SystemsYes
Gas or Oil HeatYes
Electric FurnaceYes
Hydronic (Hot Water) Zone Heat - 2 WiresYes
Hydronic (Hot Water) Zone Heat - 3 WiresYes
Wired Remote Temperature Sensor (Indoor or Outdoor)Yes

Precautions

CAUTION! To prevent electrical shock/equipment damage, disconnect power at main fuse/circuit breaker until installation complete. Label wires prior to disconnection. If in doubt about wiring, consult qualified heating/air conditioning contractor.

WARNING! Do not use on circuits exceeding 20-30 VAC 50/60 Hz (1.5A per terminal, 2.5A max total); higher voltage damages control/causes shock/fire. Do not short terminals on gas valve/primary control to test; short/incorrect wiring burns out components/causes injury/property damage. Conform to NEC Class II circuits. Do not operate cooling below 50°F (compressor damage).

ATTENTION! This product does not contain mercury but may replace one that does. Do not open mercury cells; if damaged, wear non-absorbent gloves, clean up spilled mercury, place in sealed container. Refer to www.white-rodgers.com for disposal. Touch side of thermostat to release static before touching keys.

Specifications

Removing Old Thermostat

A standard heat/cool thermostat consists of basic parts: Cover, Base, Subbase. Label each wire with terminal designation before disconnecting. Disconnect wires one at a time; do not let fall into wall.

Installation

Remove old thermostat. Mount new base level on wall, connect wires to terminals. Push excess wire into wall, secure base, attach thermostat body. Power up and configure.

Batteries: Install 2 AA alkaline batteries; low battery indicated on display.

Wiring Diagrams

Terminal Designations: R (24V hot), C (common), Y (compressor), G (fan), W (heat), O/B (changeover), E (emergency), L (fault/alert).

Single Stage Heat/Cool: R to hot, C to common, Y to compressor, G to fan, W to heat.

Heat Pump: Y compressor, O/B changeover (O cool, B heat).

Heat Only: W heat relay/valve.

Cool Only: Y compressor relay.

Millivolt: W millivolt gas valve.

Hydronic: W zone valve/circulator.

Remote Sensor: Terminals for indoor/outdoor wired sensor.

CAUTION! Refer to equipment manuals for specifics. Do not short wires.

Check Operation

Restore power. Set SYSTEM to HEAT/COOL, FAN to ON/AUTO, adjust setpoint to test.

Fan Operation

  1. FAN ON: Blower runs continuously.
  2. FAN AUTO: Blower runs on call for heat/cool.

Heating System

  1. SYSTEM HEAT.
  2. Setpoint above room temp: Heat activates.
  3. Setpoint below: Heat stops.

Emergency System

  1. SYSTEM EM HEAT (for heat pumps).
  2. Setpoint above: Emergency heat operates.
  3. Setpoint below: Stops.

Cooling System

CAUTION! Do not operate below 50°F.

  1. SYSTEM COOL.
  2. Setpoint below room temp: Cool activates.
  3. Setpoint above: Cool stops.

Operating Features

Programming

Non-programmable with optional 7-day factory pre-program for energy savings. Activate by setting clock and pressing RunSched.

  1. Set Time: Press Menu > Time, adjust hour/min/AM/PM/day.
  2. Pre-Program: Press RunSched to activate factory schedule (all days: similar to standard wake/work/home/sleep setpoints).
  3. Auto Schedule: Copies current temps for periods, night setback 6°F.
  4. Fan Program: Set fan on/off times for heat/cool periods.

Installer Configuration

Press and hold Menu for 5 seconds to enter menu. Use up/down to adjust, Menu to advance.

Menu ItemFactory DefaultOptionsComments
1) GAS or ElectricGASGAS/ELEHeating system type
2) Change FilterOFFOFF, 30-2000 hFilter reminder interval
3) Change UV LampOFFOFF, 30-350 daysUV lamp reminder
4) Cool Onoo/fCooling cycle rate
5) Heat Offoo/fHeating cycle rate
6) Heat Onoo/fHeating cycle rate
7) Fan Onoo/fFan cycle rate
8) Heat Pumpoo/fHeat pump cycle
9) Emergency Heatoo/fEmergency cycle
10) Compressor Protection50-5 minMin off time
11) Heat Pump Balance Point55°F25-45°FAux switch temp
12) Heat Pump Changeover45°F25-85°FHeat/cool changeover
13) Auto Changeoveroo/fEnable auto changeover
14) Remote Sensoroo/fEnable remote sensor
15) Auto Schedule Copyoo/fCopy for auto schedule

Troubleshooting

SymptomPossible CauseCorrective Action
Display Blank/ErraticVoltage spike/static.Remove R/C wires (no short), remove batteries 2 min, reinstall/configure.
System Not RespondingWiring/config issue.Check wiring/manual; contact service person.
Batteries LowLow power.Replace with 2 new premium AA alkaline.
Filter/UV ReminderInterval reached.Change and reset via Menu.
Fan Not RunningAUTO no call; wiring.Set ON; check G terminal.
Short CyclingCycle settings.Adjust in menu.
Compressor Won't StartProtection lockout.Wait 5 min; check indicators.