The White Rodgers 1F97W-71 is a 7-day programmable electronic digital thermostat from the Comfort-Set series for single-stage heat/cool or heat pump systems. It features 7-day programming with 4 periods per day, automatic/manual changeover, Computed Energy Management Recovery (EMR), compressor short cycle protection, backlit display, and 3 AA battery backup. Powered by 24 VAC; compatible with systems up to 1.5A per terminal, 1.5A max total. Below are the key specifications, installation, operation, programming, and troubleshooting instructions.
Assemble tools: hand or power drill with 3/16 inch drill bit (if needed), flat blade screwdriver, wire cutter/stripper, level, voltmeter. Shut off electricity at main fuse box until installation complete. Label wires before disconnecting. This thermostat is for 24V systems only; not for line voltage. Install away from drafts, direct sunlight, or heat sources for accurate sensing. Install 3 AA Energizer alkaline batteries before programming.
WARNING! Failure to read and follow all instructions carefully before installing or operating this control could cause personal injury and/or property damage. Save these instructions.
The thermostat uses solid-state microcomputer technology to provide precise time/temperature control. Features 7-day programming with four time/temperature settings per day, simultaneous heat/cool programs, EMR, automatic changeover (selectable), compressor protection, fan auto/on, backlit LCD display, F/C convertibility, audio prompting, system indicator light. LCD display shows time/room temp/setpoint, up/down arrows, SYSTEM switch (HEAT/OFF/COOL/AUTO), FAN switch (ON/AUTO). Terminals: R (hot), C (common), G (fan), Y (compressor), W (heat), O/B (changeover).
Applications: Single-Stage Heat Pump: Yes; Heat Pump with Aux: No; Single-Stage Conventional: Yes; Heat Only: Yes; Cool Only: Yes; Gas/Oil/Electric/Hydronic: Yes; Millivolt: Yes.
CAUTION! To prevent electrical shock/equipment damage, disconnect power at main fuse/circuit breaker until installation complete. Label wires prior to disconnection. If in doubt about wiring, consult qualified heating/air conditioning contractor.
WARNING! Do not use on circuits exceeding 17-30 VAC 50/60 Hz (0.05-1.5A per terminal, 1.5A max total); higher voltage damages control/causes shock/fire. Do not short terminals on gas valve/primary control to test; short/incorrect wiring burns out components/causes injury/property damage. Conform to NEC Class II circuits. Do not operate cooling below 50°F (compressor damage).
ATTENTION! This product does not contain mercury but may replace one that does. Do not open mercury cells; if damaged, wear non-absorbent gloves, clean up spilled mercury, place in sealed container. Refer to www.thermostat-recycle.org for disposal. Handle to avoid static discharge.
A standard heat/cool thermostat consists of three basic parts: 1) Cover; 2) Base; 3) Subbase. Label each wire with terminal designation before disconnecting. Disconnect wires one at a time; do not let fall into wall.
Remove old thermostat. Mount new subbase level on wall, connect wires to terminals. RED jumper between RH and RC for single transformer systems. Push excess wire into wall, secure subbase, attach thermostat body (set switches and program with batteries first). Power up and configure.
Batteries: Install 3 AA Energizer alkaline; low battery flashes "BATTERY" and beeps every 5 min. Replace if low; program retained.
Terminal Designations: RH/RC (hot), C (common), G (fan), Y (compressor), W (heat), MV (millivolt).
Heat Only (2-Wire): RH/RC jumper, W to heat.
Millivolt: MV to gas valve.
Millivolt + Cool: MV to heat, Y to cool.
Heat Only (3-Wire Zone): R to power, W to valve, C common.
Heat/Cool (5-Wire): R to power, W heat, Y cool, G fan, C common.
CAUTION! Refer to equipment manuals for specifics. All wiring per local codes.
Restore power. Set SYSTEM to HEAT/COOL, FAN to ON/AUTO, adjust setpoint to test.
CAUTION! Do not operate below 50°F.
7-day programming; 4 periods per day. Factory preprogrammed; use VIEW PRGM to review.
Factory Heat: All days 6AM 70°F, 8AM 62°F, 5PM 70°F, 10PM 62°F. Cool: 6AM 78°F, 8AM 85°F, 5PM 78°F, 10PM 82°F.
Set option switches on back before installation.
| Group/Switch | Setting | Options | Comments |
|---|---|---|---|
| Group A #1/#2 | OFF/OFF | ON/OFF | Total Keypad Lockout (ON/OFF) |
| Group B #1/#2 | OFF/OFF | OFF/ON | Auto Changeover (OFF=Auto, ON=Manual) |
| Group B #3 | OFF | ON/OFF | EMR (ON=Enabled) |
| Anticipation Heat | 4 | 2-40 | Adjust cycle rate |
| Anticipation Cool | 2 | 4-40 | Adjust cycle rate |
| °F/°C | °F | °F/°C | Temperature scale (press TIME + BACK) |
| Symptom | Possible Cause | Corrective Action |
|---|---|---|
| Program lost after power outage | No/dead batteries | Install/replace 3 AA Energizer alkaline. |
| Display flashes BATTERY, beeps every 5 min | Low battery | Replace batteries. |
| Temp not changing at program time | Blower delay | Allow time for air dissipation. |
| System turns on/off frequently | Anticipation too low | Increase heat 4, cool 2. |
| System turns on/off seldom | Anticipation too high | Decrease anticipation. |
| Spark discharge on touch | Static in low humidity | Remove from wall, disconnect battery. |
| Temp changes below setpoint | Outside <50°F | Avoid lowering cool setpoint; risk damage. |