The White Rodgers SuperStat Pro is a 5+2 day programmable electronic digital thermostat for low voltage heating and cooling systems. It features separate weekday/weekend programming with 4 periods per day, simultaneous heat/cool programs, automatic/manual changeover, compressor protection, filter reminder, and energy usage display. Powered by 24 VAC; compatible with single-stage systems up to 1.5A per terminal, 1.5A max total. Below are the key specifications, installation, operation, programming, and troubleshooting instructions.
Assemble tools: hand or power drill with 3/16 inch drill bit (if needed), flat blade screwdriver, wire cutter/stripper, level, voltmeter. Shut off electricity at main fuse box until installation complete. Label wires before disconnecting. This thermostat is for 24V systems only; not for line voltage. Install away from drafts, direct sunlight, or heat sources for accurate sensing. Install 3 AA Energizer alkaline batteries before programming.
WARNING! Failure to read and follow all instructions carefully before installing or operating this control could cause personal injury and/or property damage. Save these instructions.
The thermostat uses solid-state microcomputer technology to provide precise time/temperature control. Features 5+2 day programming with four time/temperature settings per day, simultaneous heat/cool programs, automatic/manual changeover, compressor protection, filter reminder, energy usage display, backlit LCD. LCD shows time/room temp/setpoint, up/down arrows, SYSTEM switch (HEAT/OFF/COOL/AUTO/EMER), FAN switch (ON/AUTO), buttons for RUN, HOLD, INFO, PRGM, DEVICE/MODE, TIME/SET, DAY/PERIOD. Terminals: R (hot), C (common), G (fan), Y (compressor), W (heat), O/B (changeover).
Applications: Single-Stage Heat/Cool: Yes; Heat Only: Yes; Cool Only: Yes; Heat Pump (Single-Stage): Yes; Gas/Oil/Electric/Hydronic: Yes; Millivolt: Yes.
CAUTION! To prevent electrical shock/equipment damage, disconnect power at main fuse/circuit breaker until installation complete. Label wires prior to disconnection. If in doubt about wiring, consult qualified heating/air conditioning contractor.
WARNING! Do not use on circuits exceeding 24 VAC 50/60 Hz (1.5A per terminal, 1.5A max total); higher voltage damages control/causes shock/fire. Do not short terminals on gas valve/primary control to test; short/incorrect wiring burns out components/causes injury/property damage. Conform to NEC Class II circuits. Do not operate cooling below 50°F (compressor damage). Avoid overriding Critical Events to prevent higher energy costs.
| Feature | Detail |
|---|---|
| Power | Powered by indoor air handler or 120V outlet (gas furnace) |
| Accuracy | ±1.0°F |
| Battery Backup | Maintains time and temperature during power loss |
| Display | Alternates time and temperature setpoint |
| Modes | HEAT, COOL, AUTO, EMER (heat pumps), OFF |
Remove old thermostat. Mount new base level on wall, connect wires to terminals. Push excess wire into wall, secure base, attach thermostat body. Power up and configure. For filter reset: Press RUN and HOLD simultaneously after changing filter.
Terminal Designations: R (hot), C (common), G (fan), Y (compressor), W (heat), O/B (changeover).
Single Stage Heat/Cool: R to hot, C to common, Y to compressor, G to fan, W to heat.
Heat Only: R to hot, W to heat.
Cool Only: R to hot, Y to compressor, G to fan.
Heat Pump (Single Stage): R to hot, Y to compressor, O/B to changeover.
CAUTION! Refer to equipment manuals for specifics. All wiring per local codes.
Restore power. Set SYSTEM to HEAT/COOL, FAN to ON/AUTO, adjust setpoint to test.
CAUTION! Do not operate below 50°F.
5+2 day programming; 4 periods (Morning, Day, Evening, Night). Factory preprogrammed; press PRGM to enter.
Factory Pre-Program (All Days):
| Period | Time | Heat | Cool |
|---|---|---|---|
| Morning | 6:00 AM | 70°F | 78°F |
| Day | 8:00 AM | 62°F | 85°F |
| Evening | 5:00 PM | 70°F | 78°F |
| Night | 10:00 PM | 62°F | 82°F |
No dedicated installer menu mentioned; configuration via programming and mode switches.
| Symptom | Possible Cause | Corrective Action |
|---|---|---|
| Blank Display | Power loss. | Check power to air handler or 120V outlet. |
| Flashing Display | Normal or Critical Event. | Normal operation; overrides cost more for 8 hours. |
| Fading Display | Thermostat failure. | Call 1-888-232-5940 for service. |
| Incorrect Temperature | Setpoint or Critical Event. | Adjust setpoint; check event recovery. |
| Fan Not Turning On/Off | Delay in gas furnace. | Up to 90 sec normal; check settings. |
| Heating/Cooling Not Working | Mode, breaker, settings. | Verify mode (HEAT/COOL), breakers, STG display. |